Differential pressure transmitter TRDU

Gram pressure transmitter is excellent as signaller for frequency converters (with PID-regulation). Available in two types for pressure ranges from 0 to 50 kPa.
Differential pressure transmitters are ideal for reference signal for units with constant vacuum. Both types have a compact design and are equipped with screw holes for wall mounting. Are delivered incl. connection piece and 2m sensor hose.

Product Features

  • Quick and easy mounting
  • Supply: 10-35 VDC (2-cable supply)
  • Favorable price
  • Advantageous performance ratio

Further data

  • Gram pressure transmitters are especially suitable as signaller for frequency converters (with PID-regulation).
  • Emits a signal signal 4-20mA, dependant on sensing of actual vacuum on the ventilation system.

Type 1 (photo above):

Intended for pressure range: 0-1.25 and 0-5 kPa.

Order no. Type Pressure
range
[kPa]
Ambient
temperature
[°C]
Medium
temperature
[°C]

Weight
[g]

Sensor
hose
connection
Form Cable gland Protection
rating
 09 370 400  1  0 - 1,25  -18° - 66°C  -18° - 66°C  230  ø5.0mm

Round

 5-10mm  IP66
09 370 500  1  0 - 5  -18° - 66°C  -18° - 66°C  230  ø5.0mm

Round

 5-10mm  IP65
 09 371 500  2  0 - 10  -15° - 60°C   -5° - 45°C  249  ø4.7mm

Square

 Hole for Pg11  IP66
 09 372 500  2  0 - 25  -15° - 60°C   -5° - 45°C  249  ø4.7mm

Square

 Hole for Pg11  IP66
 09 373 500  2  0 - 50  -15° - 60°C   -5° - 45°C  249  ø4.7mm

Square

 Hole for Pg11  IP66

 

Type 2 (photo left):

Intended for pressure range: 0-10, 0-25 and 0-50 kPa.