• Home
  • Products
  • Differential pressure control ECO-S 4, 6, 12 and 20

Differential pressure control ECO-S 4, 6, 12 and 20

Controls cleaning of compressed-air cleaned filter units. Cleans at a very high differential pressure above the filter cartridges. When the fan stops, the automatic after-cleaning begins
ECO-S is mounted directly on the filter unit, where the individual jet valves are connected with control. Further the control is connected on the raw air and clean air side of the filter cartridges by sensor hoses.

Product Features

  • Control ECO-S provides sustantial energy consumption optimization
  • Only filter cartridge cleaning as needed
  • Protects the filter cartridges
  • Easy programming
  • Shows differential pressure on display

Further data

  • ECO-S filter controls are available in 4 sizes, where they can control from 4 to 20 valves.
  • At filter unit delivery the pressure control settings has been made by the factory.
  • If it is requested other settings can easily be done.
  • Please, note: Since the filter cartridges are only cleaned when needed, this provides a great saving on the energy consumption.
  • Differential pressure filter control TBB can give an alarm at exceeded max. differential pressure.
  • The control ECO-S can be set to both 115 and 230V supply.
Technical data:
Power supply: 115V AC & 230V AC 50/60 Hz
Power consumption: 50W (2 amp)
Output voltage: 24-115-230 VAC / 24 VDC
Temperature range: - 10 ± +50°C
Visual indicators: 10,000 Pa
Setting: Keyboard
Protection rating / box: IP56
dP-control: Internal dP-sensor
Terminals: 2.5 mm2 250 VAC/12A
Weight: 1.6 kg